Print

LenelS2 Integration

NetLink integration with LenelS2 OnGuard provides full power system monitoring and control capabilities to OnGuard.  Power system alerts, parameter measurements, and system control features are all available directly from the OnGuard interface, streamlining system maintenance and maximizing system uptime.

Integration to OnGuard is through integration software via OAAP. 

LenelS2 OAAP Integration

LenelS2 OnGuard
 
 
 
 
 
Download
DescriptionLatest RevisionSoftware FileUser ManualRelease Notes
LenelS2 OnGuard Integration1.12DownloadIMRN

Requirements & Information
ItemInformation
OnGuard Version Supported7.6, 8.0
OnGuard License RequiredYes - See Below
NetLink Boards SupportedNL2, NL4, NLX
NetLink Minimum Firmware Version9.18 or above
Integration TypeSNMP Trap
Integration LevelAlerts

License  Numbers (Purchased through LenelS2)
SKUDescription
IPC-321-LSP01-BIf System Purchased Through LenelS2 Direct - Initial License - 10 Panels / power devices
IPC-321-010If System Purchased Through LenelS2 Direct - License and support of 10 additional panels / power devices
IPC-344-LSPZ01-BIf System Not Purchased Through LenelS2 Direct - Initial License - 10 Panels / power devices
IPC-344-010If System Not Purchased Through LenelS2 Direct - License and support of 10 additional panels / power devices
Contact LenelS2 for more licensing information.

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage 
Power Supply Output Voltage 
Power Supply Total Output Current 
Battery Voltage 
Battery Charge / Discharge Current 
M8 Output (Lock) Voltage 
M8 Output (Lock) Current 
M8 Output (Lock) Cycle Count 
Enclosure Temperature 
External Temperature (IDF Closet) 
Current Sensor Measurement 
Auxiliary Voltage Measurement 

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test 
Power Cycle M8 Output 
Power Cycle Power Supply Main Output 
NetLink Control 1 / Control 2 Outputs