Home Products Boards & Components C4/C8 Lock Control
PDF Print E-mail

Power Controller Modules

Expand the number of system power outputs
controlled by the access control system.
Program for fail-safe, fail-secure, dry contact
or continuous voltage output
more information

controllermodule
 
  • Products

  • Overview

  • Technical Documents


Model # Zone count Current per zone Power limited
C4 4 3A No
C4P 4 2.5A Yes
C8 8 3A No
C8P 8 2.5A Yes
C4 / C8 Fuse protected
C4P / C8P PTC circuit breaker protection, Class 2 Power Limited

Flexibility

  • Simple field selectable switch sets either 12 or 24V DC output
  • FlexConnect system minimizes installation labor by using board buss structure to eliminate accessory board interwiring
  • Configuration jumpers are colored by function for ease of programming
        - FAI

        - NC/NO input

        - WET/DRY output

        - V SELECT

      - FAIL SAFE/SECURE output

Expandability

  • Expand number of voltage outputs in increments of eight
  • Add FAI functionality on a per zone basis
  • Add simultaneous failsafe – failsecure voltage outputs
  • Pre-punched cabinet layout allows expansion board additions with minimal labor

C4 and C8 power controller modules provide 4 or 8 relay controlled, protected outputs and 4 or 8 access control inputs. When used in a single voltage system, each individual output may be programmed for a continuous output or to respond to the input from the access control system. A fire alarm interface to over ride the access control system for control of egress locks is provided for each output. When used in a dual voltage system, each individual output zone may be programmed to operate with either of the two system voltages.

Product highlights

  • Listed for Fire Alarm, Intrusion, Access Control, CCTV and Mass Notification
  • Provides 4 or 8 trigger input zones for interface to an access control system
  • Provides 4 or 8 relay controlled output zones
  • Accommodates failsafe or failsecure locking devices
  • Provides fire alarm interface for egress lock control
  • Monitors fuse integrity of output zones and reports fault to host power supply
  • Status LEDs report zone activity
  • Each output zone is fused at 3A or 2.5A for PTC circuit breakers
  • PTC versions are low voltage, Class 2 power limited
  • Allow selection by zone from two voltage sources

Reliability and Safety

  • Lifetime warranty
  • Easily obtainable and replaceable automotive style ATM fuses

Agency Listings

USA
  • UL 294 / UL 603 / UL 1076
  • FCC Part 15, Subpart B
CANADA
  • ULC S318 / ULC S319
  • CSA C22.2 # 205
agency box

Product Warranty


Model # Datasheet Install Manual CAD Files Agency
C4 DS IM CAD AG